| INPUT |
| Voltage |
1 Phase 220 Vac, 3 Phase 220 / 380 Vac |
| Voltage Tolerance |
± 15% |
| Frequency |
50 / 60 Hz |
| Frequency Tolerance |
± 10% |
| Power Factor |
1 Phase: 0,85 / 3 Phase. 0,92 |
| OUTPUT |
| Voltage |
24, 48, 110, 220 Vdc, -10%
+35% (front panel
selectable) |
| Current |
15, 30, 60, 100 A |
| Current Limiting |
I nomx102%
Front panel selectable between 0 ile 102% |
| Ripple |
< 0,5% |
| Voltage Regulation |
±0,5% at float charge, ±1% at
boost charge |
| Efficiency |
3 Phase: >92% / 1 Phase >85% |
| Protection |
Input (thermal/magnetic) fuses, Output fuses,
Advanced short circuit protection,Overvoltage protection, Overcurrent
protection,Automatic restart |
| Battery Charge Modes(Adjustable charging voltages) |
Automatic charge,boost charge: 2,4 V / cellFloat
charge: 2,25 V / cell |
| Boost Charge Time |
Incrementable by 1 hour up to 24 hours |
| LCD Properties |
2x16 character-wide display, showing:Output
Voltage& current, load (%), Fault notices, 50 entry memory
with time&date, Output voltage high/low |
| Displays |
AA (AC available),Fault,Current limiting, Automatic
charge,Float charge,Boost Charge,Common alarm |
| Operation and Control |
Via menu selections from buttons on front panel |
| Alarms |
Common relay contact output for AA input low,
DA output low and overheat |
| Endurable Dielectric Voltage |
2000 V Input-Output |
| |
2000 V Input-Chasis |
| |
500 V Output-Chasis (for PS with output voltage
< 50V ) |
| |
1000 V Output-Chasis (for PS with output voltage
> 50V ) |
| Case Dimensions (WxDxH) |
3 Phase: 375x220x600 / 1 Phase: 300x190x450
(mm.) |
| Protection Class |
IP 20 |
| Audible Noise @1m. |
50 dBA |
| Cooling System |
Mandatory Cooling (Fan) |
| Weight |
1 Phase PS < 40 kg
3 Phase PS < 50 kg |
| Operating Temperature |
0 ēC
. 40 ēC |
| Storing Temperature |
- 20 ēC
. 70 ēC |
| Relative Humidity |
98% |
| Standards |
VDE, DIN 41773 |
| |
(Battery Charge Characteristics) |
| |
ANSI NEMA PE 5 |
| |
TS 2000 |